| dc.contributor.author | BOSNEAGA, Valeriu | |
| dc.contributor.author | SUSLOV, Victor | |
| dc.contributor.author | STRATAN, Ion | |
| dc.date.accessioned | 2025-04-25T06:13:41Z | |
| dc.date.available | 2025-04-25T06:13:41Z | |
| dc.date.issued | 2024 | |
| dc.identifier.citation | BOSNEAGA, Valeriu; Victor SUSLOV and Ion STRATAN. Distribution of symmetrical current components along 10 kv cable line with isolated neutral at single-phase fault in the medium part of the line. In: 13th IEEE International Conference and Expositions on Electric and Power Engineering, Romania, Iasi, 17-19 October, 2024. Institute of Electrical and Electronics Engineers, 2024, pp. 41-46. ISBN 979-83-50356-20-5, eISBN 979-83-50356-19-9. | en_US |
| dc.identifier.isbn | 979-83-50356-19-9 | |
| dc.identifier.isbn | 979-83-50356-20-5 | |
| dc.identifier.uri | https://doi.org/10.1109/EPEi63510.2024.10758079 | |
| dc.identifier.uri | https://repository.utm.md/handle/5014/31023 | |
| dc.description | Access full text: https://doi.org/10.1109/EPEi63510.2024.10758079 | en_US |
| dc.description.abstract | In the work is investigated the distribution of the values of the symmetrical components of capacitive currents along a 10 kV cable line with in insulated neutral mode during a single-phase ground fault in the middle part of the line. The patterns of changes of real phase currents and their symmetrical components along the line during a single-phase to ground fault are described. The distribution of currents along the length in the presence of parallel lines, one of which is damaged, has been studied. A digital model of the line and supply transformer was used, which allows obtaining results taking into account many factors that are difficult to consider in analytical form. | en_US |
| dc.language.iso | en | en_US |
| dc.publisher | Institute of Electrical and Electronics Engineers | en_US |
| dc.rights | Attribution-NonCommercial-NoDerivs 3.0 United States | * |
| dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/3.0/us/ | * |
| dc.subject | symmetrical components | en_US |
| dc.subject | high voltage cable line | en_US |
| dc.subject | isolated neutral | en_US |
| dc.subject | distribution along the line | en_US |
| dc.title | Distribution of symmetrical current components along 10 kv cable line with isolated neutral at single-phase fault in the medium part of the line | en_US |
| dc.type | Article | en_US |